Harmonics Mitigation of Stand‑Alone Photovoltaic System Using LC Passive Filter
Loading...
Date
2021
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Journal of Electrical Engineering & Technology
Open Access Color
OpenAIRE Downloads
OpenAIRE Views
Abstract
This article investigates modeling and simulation of the of-grid photovoltaic (PV) system, and elimination of harmonic components using an LC passive flter. Pulse width modulation (PWM) inverter is used to convert the direct current to
alternating current. It is very important in terms of energy quality that the inverter output current total harmonic distortion (THDI) is below the value given by standards. Harmonic components have negatively efect on of-grid PV power system.
THDI should be kept below a certain level in order to prevent damage to the equipment in the of-grid system and to ensure a higher quality energy fow to reduce the total harmonic distortion (THD) of the solar inverter output current; LC passive
flter must be connected to the output of the PWM inverter. There are many types of passive flters for solar inverters. One of
the most widely used flter types is the LC flter. LC flters are used in of-grid systems. LC flter is smaller in size and lower
cost than other flters. But it is more complicated to determine the parameters of the LC flter. Therefore, in order for the system to remain in a steady state, the parameters must be accurately calculated and analyzed. In this study, the output power
of the solar inverter, switching frequency, bus voltage etc. values were determined and LC flter parameters were calculated. Since high inductance values are used in LC flters, the voltage drop increases in these flters. To reduce the voltage drop, the
DC bus voltage must be increased, which increases the switching losses. LC flter is connected between the inverter and the nonlinear load to flter the harmonic components produced by the DC/DC boost converter, DC/AC inverter and non-linear load. Matlab/Simulink program was used in Simulation and analysis of of-grid solar system. Solar inverter output current THD was measured as 91.55%. After the LC flter is connected to the system, this value has dropped to 2.62%.
Description
ORCID
Keywords
Six-pulse rectifer ·, Total harmonic distortion for current ., Passive LC flter ·, Of-grid photovoltaic system
Turkish CoHE Thesis Center URL
Fields of Science
Citation
WoS Q
Q3
Scopus Q
Source
Journal of Electrical Engineering & Technology
Volume
16
Issue
Start Page
2389
End Page
2396